Mitsubishi Electric 800 Series Instruction Manual page 526

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 BINARY VALUE
Object
Object name
identifier
0
Inverter running
11
Inverter operation
ready
98
Alarm output
99
Fault output
200
Inverter running
reverse
300
Control input
instruction AU
301
Control input
instruction RT
302
Control input
instruction RL
303
Control input
instruction RM
304
Control input
instruction RH
305
Control input
instruction JOG
306
Control input
instruction MRS
307
Control input
instruction STOP
308
Control input
instruction RES
309
Control input
instruction CS
400
Run/Stop
401
Forward/Reverse
402
Fault reset
*1
R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array, even when "Write Access Denied" is returned
due to inconsistency of the writing requirements such as the operating mode, on condition that the values are written within the setting range.
*2
The following signals cannot be controlled by the network: Jog operation, selection of automatic restart after instantaneous power failure, start
self-holding, and reset. Therefore control input instruction JOG, STOP, RES, and CS are invalid in the initial status. To use the control input
instruction JOG, STOP, RES, and CS, change the signals with Pr.185, Pr.186, Pr.188, Pr.189 (Input terminal function selection). (Refer to
page
343.) (Reset is available with ReinitializeDevice.)
*3
If communication operation command source is other than NET, the setting value can be written, but not to be applied.
Present value
*1
access type
R
Represents inverter running (RUN signal) status.
R
Represents inverter operation ready (RY signal) status.
R
Represents alarm output (LF signal) status.
R
Represents fault output (ALM signal) status.
R
Represents inverter reverse running status.
C
Controls the function assigned to terminal AU.
Setting 1 in this object turns ON the signal assigned to Pr.184 AU terminal
function selection.
C
Controls the function assigned to terminal RT.
Setting 1 in this object turns ON the signal assigned to Pr.183 RT terminal
function selection.
C
Controls the function assigned to terminal RL.
Setting 1 in this object turns ON the signal assigned to Pr.180 RL terminal
function selection.
C
Controls the function assigned to terminal RM.
Setting 1 in this object turns ON the signal assigned to Pr.181 RM terminal
function selection.
C
Controls the function assigned to terminal RH.
Setting 1 in this object turns ON the signal assigned to Pr.182 RH terminal
function selection.
C
Controls the function assigned to terminal JOG.
*2
Setting 1 in this object turns ON the signal assigned to Pr.185 JOG terminal
function selection.
C
Controls the function assigned to terminal MRS.
Setting 1 in this object turns ON the signal assigned to Pr.187 MRS terminal
function selection.
C
Controls the function assigned to terminal STOP.
*2
Setting 1 in this object turns ON the signal assigned to Pr.188 STOP
terminal function selection.
C
Controls the function assigned to terminal RES.
Setting 1 in this object turns ON the signal assigned to Pr.189 RES terminal
*2
function selection.
C
Controls the function assigned to terminal CS.
Setting 1 in this object turns ON the signal assigned to Pr.186 CS terminal
*2
function selection.
C
Controls the start/stop command. The start command is written after the
Speed scale is applied.
1: Start
0: Stop
C
Controls the forward/reverse rotation.
1: Reverse rotation
0: Forward rotation
C
Clears fault output status.
(Release of an inverter fault without inverter reset is available.)
Description
*3
*3
5.12 (N) Operation via communication and its settings
3
4
5
5
5
6
7
8
9
10
525
5. PARAMETERS