5.5.3
Remote setting function
Even if the operation panel is located away from the enclosure, contact signals can be used to perform continuous variable-
speed operation, without using analog signals.
Pr.
Name
59
Restart cushion time
F101
 Remote setting function
• When Pr.59 ≠ "0" (remote setting enabled), the functions of the signals are as shown in the following table.
Signal name
STF/STR
RH
RM
RL
Terminal 2 (analog signal)
Inverter
Forward
rotation
STF
Acceleration
RH
Deceleration
RM
10
Clear
RL
2
SD
5
Connection
diagram for remote setting
 Main speed
• The main speed used in the remote setting corresponds with each of the following operation modes.
PU operation mode / NET operation mode
External operation mode / PU/External combined operation mode 2 (Pr.79 = "4")
PU/External combined operation mode 1 (Pr.79 = "3")
*1
Set Pr.28 Multi-speed input compensation selection to "1" when enabling compensation for input via terminal 1.
Initial
Setting
value
range
0
0
1
2
3
11
12
13
Function
Forward/Reverse
Acceleration
Deceleration
Clear
Main speed
Set frequency
Increased
(Hz)
according to the
Pr.44 setting
Terminal 2
(main speed)
RH (Acceleration)
RM (Deceleration)
RL (Clear)
STF (Forward)
Operation mode
5.5 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
RH, RM, RL signal
Frequency setting
function
storage function
Multi-speed setting
-
Remote setting
With
Remote setting
Without
Remote setting
Without (Turning
STF/STR OFF clears
remotely-set
frequency.)
Remote setting
With
Remote setting
Without
Remote setting
Without (Turning
STF/STR OFF clears
remotely-set
frequency.)
Description
The inverter accelerates the motor in the forward or reverse direction up to
the main speed or to the frequency stored by the remote setting function.
The set frequency increases according to the Pr.44 setting.
The set frequency decreases according to the Pr.45 setting.
The set frequency is cleared and the main speed is applied.
The setting of the main speed is used as a base. The main speed is
increased by the RH signal and decreased by the RM signal.
Decreased according to
the Pr.45 setting
ON
ON
ON
Digital setting
Analog input
Analog input via terminal 4 (AU signal ON)
Description
Deceleration to the
frequency lower
than the set
frequency
Disabled
Enabled
Cleared by RL
Time
ON
Main speed
*1