 Connection of RS-485 terminals and wires
• The size of RS-485 terminal block is the same as the control circuit terminal block. Refer to
NOTE
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
• When the FR-F860-00680 or higher is used with a plug-in option, lead the wires on the left side of the plug-in option for
wiring of the RS-485 terminals.
 System configuration of RS-485 terminals
• Computer and inverter connection (1:1)
RS-485
interface/
terminals
• Combination of computer and multiple inverters (1:n)
Computer
RS-485
interface terminals
Computer
RS-232C
converter
RS-232C
cable
Converter
476
5. PARAMETERS
5.12 (N) Operation via communication and its settings
Computer
Inverter
RS-485
terminals
Twisted pair cable
Station 0
Inverter
RS-485
terminals
Twisted pair cable
Station 0
Inverter
RS-485
Maximum
terminals
15 m
Twisted pair cable
Computer
RS-232C
cable
Converter
∗Set the terminating resistor switch to the "100 Ω" position.
Station 1
Station n
Inverter
Inverter
RS-485
RS-485
terminals
terminals
Station 1
Station n
Inverter
Inverter
RS-485
RS-485
terminals
terminals
page 56
for the wiring method.
Inverter
RS-485
terminals
Maximum
15 m
Twisted pair cable
∗Set only the terminating resistor switch of the
remotest inverter to the "100 Ω" position.
∗Set only the terminating resistor switch of the
remotest inverter to the "100 Ω" position.