5.6.1
Operation mode selection
Select the operation mode of the inverter.
The mode can be changed among operations using external signals (External operation), operation by operation panel or the
parameter unit (PU operation), combined operation of PU operation and External operation (External/PU combined operation),
and Network operation (when RS-485 terminals or communication option is used).
Pr.
79
Operation mode selection
D000
The following table lists valid and invalid commands in each operation mode.
Pr.79
setting
0
External/PU switchover mode.
(initial
The inverter operation mode can be switched between PU and External by pressing
value)
.
At power ON, the inverter is in the External operation mode.
Operation mode
1
PU operation mode fixed
2
External operation mode
fixed.
The operation can be
performed by switching
between the External and
NET operation modes.
3
External/PU combined
operation mode 1
4
External/PU combined
operation mode 2
6
Switchover mode
Switching of PU, External, and NET operation modes can be performed during
operation.
7
External operation mode (PU operation interlock)
X12 signal ON: Switchover to PU operation mode enabled (during External operation,
output shutoff)
X12 signal OFF: Switchover to PU operation mode disabled
*1
The priority of frequency commands when Pr.79 = "3" is "multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog input
(AU) > digital input by operation panel".
204
5. PARAMETERS
5.6 (D) Operation command and frequency command
Name
Initial value
0
Description
Frequency command
Operation panel or
parameter unit.
External signal input
(terminal 2 and 4, JOG,
multi-speed selection, etc.)
Operation panel/parameter
unit or external signal input
(multi-speed setting,
*1
terminal 4)
External signal input
(terminal 2 and 4, JOG,
multi-speed selection, etc.)
Setting range
0 to 4, 6, 7
Selects the operation mode.
Operation panel display
PU operation mode
[PU]
External operation mode
[EXT]
NET operation mode
[NET]
Start command
PU operation mode
or
on
[PU]
operation panel or
parameter unit
External signal input
External operation mode
(terminal STF, STR)
[EXT]
NET operation mode
[NET]
External signal input
External/PU combined
(terminal STF, STR)
operation mode
[PU+E]
or
on
operation panel or
parameter unit
PU operation mode
[PU]
External operation mode
[EXT]
NET operation mode
[NET]
Description
Refer to
page
208
208
208
209
209
209
210