Mitsubishi Electric 800 Series Instruction Manual page 403

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Connection diagram
Sink logic
Pr.128=20
Pr.183=14
Pr.191=47
Pr.192=16
Pr.193=14
Pr.194=15
*1
Prepare a power supply matched to the power supply specification of the detector.
*2
The output signal terminal to be used differs according to the Pr.190 to Pr.196 (Output terminal function selection) setting.
*3
The input signal terminal to be used differs according to the Pr.178 to Pr.189 (Input terminal function selection) setting.
*4
The AU signal need not be input.
 Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
• Switch the power voltage/current specifications of terminals 2 and 4 by Pr.73 Analog input selection or Pr.267 Terminal
4 input selection to match the specification of the input device. After changing the Pr.73 and Pr.267 settings, check the
voltage/current input selection switch. Incorrect setting may cause a fault, failure or malfunction. (Refer to
setting.)
Pr.128
Pr.609
setting
Pr.610
0
Invalid
10
11
20
21
50
Invalid
51
60
61
70
71
80
81
90
91
100
101
402
5. PARAMETERS
5.11 (A) Application parameters
Power supply
Forward
rotation
Reverse
rotation
PID control
selection
Setting
Potentiometer
(Set point setting)
AC1φ
200/220 V 50/60 Hz
PID action
PID invalid
Reverse action
Forward action
Reverse action
Terminal 2 or Pr.133
Forward action
Reverse action
Forward action
Reverse action
Communication
Forward action
Reverse action
Forward action
Reverse action
PLC function
Forward action
(with frequency reflected)
Reverse action
Forward action
Reverse action
PLC function
(without frequency
Forward action
reflected)
Inverter
MCCB
R/L1
U
S/L2
V
T/L3
W
STF
STR
RT(X14)
∗3
∗2
(PID)SU
SD
∗2
(FUP)FU
∗2
(FDN)OL
10
2
∗2
(RL)IPF
5
1
SE
Output signal common
4
∗4
(Measured value) 4 to 20 mA
0 24 V
Power
∗1
supply
Set point input
Measured value input
*1
Terminal 4
*2
Communication
PLC function
*3
(with frequency reflected)
PLC function
(without frequency
*3
reflected)
Pump
Motor
M
P
2-wire type
During PID action
Detector
Upper limit
Lower limit
-
-
+
+
Forward rotation
output
Reverse rotation
output
(OUT)
(COM)
Deviation input
Terminal 1
Communication
*2
PLC function
(with frequency reflected)
*3
PLC function
(without frequency
reflected)
*3
3-wire
type
+
(24 V)
page 318
for the
*2
*3
*3