5.12.6
MODBUS RTU communication specification
Operation by MODBUS RTU communication or parameter setting is possible by using the MODBUS RTU communication
protocol from the RS-485 terminals of the inverter.
Pr.
331
RS-485 communication
N030
station number
332
RS-485 communication
N031
speed
N033
RS-485 communication stop
bit length
333
RS-485 communication stop
bit length / data length
334
RS-485 communication
N034
parity check selection
343
Communication error count
N080
539
MODBUS RTU
N002
communication check time
interval
549
Protocol selection
N000
NOTE
• To use the MODBUS RTU protocol, set "1" to Pr.549 Protocol selection.
• If MODBUS RTU communication is performed from the master to the address 0 (station number 0), the data is
broadcasted, and the inverter does not send any reply to the master. To obtain replies from the inverter, set Pr.331 RS-
485 communication station number  "0 (initial value)". Some functions are disabled in broadcast communication. (Refer
to
page
503.)
• If a communication option is mounted with Pr.550 NET mode operation command source selection = "9999 (initial
value)", commands (operation commands) transmitted via RS-485 terminals become invalid. (Refer to
500
5. PARAMETERS
5.12 (N) Operation via communication and its settings
Name
Initial
value
0
96
1
1
2
0
9999
0
Setting range
0
Broadcast communication
1 to 247
Inverter station number specification
Set the inverter station numbers when two or more inverters are
connected to one personal computer.
3, 6, 12, 24,
Set the communication speed.
The setting value  100 equals the communication speed.
48, 96, 192,
384, 576, 768,
For example, if 96 is set, the communication speed is 9600 bps.
1152
0
Stop bit length 1 bit
1
Stop bit length 2 bits
0
Stop bit length 1 bit
1
Stop bit length 2 bits
10
Stop bit length 1 bit
11
Stop bit length 2 bits
0
Without parity check
Stop bit length 1 bit / 2 bits (depends on the setting of Pr.333)
1
With parity check at odd numbers
Stop bit length 1 bit
2
With parity check at even numbers
Stop bit length 1 bit
Displays the communication error count during MODBUS RTU
communication. Read-only.
0
MODBUS RTU communication, but the inverter trips in the NET
operation mode.
0.1 to 999.8 s
Set the interval of the communication check (signal loss
detection) time (same specifications as Pr.122).
9999
No communication check (signal loss detection)
0
Mitsubishi inverter protocol (computer link)
1
MODBUS RTU protocol
2
BACnet MS/TP protocol
Description
Valid when Pr. N034 (334) = "0"
Valid when Pr. 334 = "0"
page
214.)