NOTE
• When performing RS-485 communication with multiple inverters, use the RS-485 terminals. (Refer to
• Computer-inverter connection cable
Refer to the following for the connection cable (RS-232C  RS-485 converter) between the computer with an RS-232C
interface and an inverter. Commercially available products (as of October 2020)
Model
Interface embedded cable
DAFXIH-CAB (D-SUB25P for personal computer side)
DAFXIH-CABV (D-SUB9P for personal computer side)
+
Connector conversion cable DINV-485CAB (for inverter side)
Interface embedded cable dedicated for inverter
*2
DINV-CABV
*2
The conversion cable cannot connect multiple inverters. (The computer and inverted are connected in a 1:1 pair.) This is an RS232C-to-RS485
converter-embedded conversion cable. No additional cable or connector is required. For the product details, contact the manufacturer.
• Use Ethernet cables compliant with the following standards when fabricating the cable.
Ethernet cable
Category 5e or higher straight cable
*3
(double shielded / STP)
*3
Do not use pins No. 2 and 8 of the communication cable.
5.12.2
Wiring and configuration of RS-485 terminals
 RS-485 terminal layout
Terminating resistor switch
Initially-set to "OPEN".
Set only the terminating resistor switch of
the remotest inverter to the "100Ω" position.
P5S
SG
SDA1
(VCC)
(GND)
(TXD1+)
OPEN
VCC GND
+ TXD
100Ω
VCC GND
+ TXD
P5S
SG
SDA2
(VCC)
(GND)
(TXD2+)
Name
RDA1 (RXD1+)
Inverter receive +
RDB1 (RXD1-)
Inverter receive -
RDA2 (RXD2+)
Inverter receive + (for branch)
RDB2 (RXD2-)
Inverter receive - (for branch)
SDA1 (TXD1+)
Inverter send +
SDB1 (TXD1-)
Inverter send -
SDA2 (TXD2+)
Inverter send + (for branch)
SDB2 (TXD2-)
Inverter send - (for branch)
P5S (VCC)
5V Permissible load current 100 mA
SG (GND)
Earthing (grounding) (connected to terminal SD)
*2
Connector
RJ-45 connector
SDB1
RDA1
RDB1
(TXD1-)
(RXD1+)
(RXD1-)
-
+
RXD
-
-
+
RXD
-
SDB2
RDA2
RDB2
(TXD2-)
(RXD2+)
(RXD2-)
Description
Manufacturer
Diatrend Corp.
Type
The following conditioning cables:
• IEEE 802.3 (1000BASE-T)
• ANSI/TIA/EIA-568-B (Category 5e)
5.12 (N) Operation via communication and its settings
3
page
476.)
4
5
5
5
6
7
8
9
10
475
5. PARAMETERS

Advertisement

Table of Contents
loading

Table of Contents