2.5.3
Applicable cables and the wiring length
Select a recommended cable size to ensure that the voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit wires will cause the motor
torque to decrease especially at a low speed.
The following table indicates a selection example for the wiring length of 20 m.
 SLD rating (Pr.570 Multiple rating setting = "0")
• 600 V class (575 V input power supply, without a power factor improving AC or DC reactor)
Applicable
Terminal
inverter model
screw
FR-F860-[ ]
size
00027 to 00090
M4
00170
M4
00320
M5
00450
M6
00680
M8
01080
M8
01440
M10
01670
M10
02430
M10
02890
M12(M10)
03360
M12(M10)
04420
M12(M10)
Applicable
Terminal
inverter model
screw
FR-F860-[ ]
size
00027 to 00090
M4
00170
M4
00320
M5
00450
M6
00680
M8
01080
M8
01440
M10
01670
M10
02430
M10
02890
M12(M10)
03360
M12(M10)
04420
M12(M10)
44
2. INSTALLATION AND WIRING
2.5 Main circuit terminals
Tightening
torque
*2
N•m
R/L1,
S/L2,
T/L3
1.5
2-4
1.5
3.5-4
2.5
8-5
4.4
14-6
7.8
22-8
7.8
26.5
26.5
26.5
46
46
46
Tightening
torque
*2
N•m
R/L1,
S/L2,
T/L3
1.5
2-4
1.5
3.5-4
2.5
8-5
4.4
14-6
7.8
22-8
7.8
26.5
26.5
26.5
46
46
46
Crimping terminal
U, V, W
P/+,
Earthing
P1
(grounding)
cable
2-4
2-4
2-4
2-4
3.5-4
3.5-4
5.5-5
8-5
5.5-5
14-6
14-6
14-6
22-8
22-8
22-8
Crimping terminal
U, V, W
P/+,
Earthing
P1
(grounding)
cable
2-4
2-4
2-4
2-4
3.5-4
3.5-4
5.5-5
8-5
5.5-5
14-6
14-6
14-6
22-8
22-8
22-8
*1
Cable gauge
HIV cables, etc. (mm
R/L1,
U, V,
P/+,
S/L2,
W
P1
(grounding)
T/L3
2
2
2
2
3.5
2
3.5
3.5
8
5.5
8
5.5
14
14
14
14
22
22
22
22
*1
Cable gauge
AWG/MCM
R/L1,
U, V,
P/+,
S/L2,
W
P1
(grounding)
T/L3
14
14
14
14
10
14
10
12
8
10
8
10
4
6
4
6
2
4
2
4
2
)
Earthing
cable
Earthing
cable