5.11.11 PID control enhanced functions
PID control enhanced functions can be used to perform PID control according to applications.
Pr.
1361
Detection time for PID
A440
output hold
1362
PID output hold range
A441
1363
PID priming time
A447
1364
Stirring time during sleep
A448
1365
Stirring interval time
A449
1366
Sleep boost level
A627
1367
Sleep boost waiting time
A628
1368
Output interruption cancel
A629
time
111
Check valve deceleration
F031
time
1369
Check valve closing
A446
completion frequency
1346
PID lower limit operation
A457
detection time
1370
Detection time for PID
A442
limiting operation
1371
PID upper/lower limit pre-
A443
warning level range
1372
PID measured value control
A444
set point change amount
1373
PID measured value control
A445
set point change rate
1374
Auxiliary pressure pump
A450
operation starting level
1375
Auxiliary pressure pump
A451
operation stopping level
1377
PID input pressure
A452
selection
1378
PID input pressure warning
A453
level
1379
PID input pressure fault
A454
level
1380
PID input pressure warning
A455
set point change amount
1381
PID input pressure fault
A456
operation selection
440
5. PARAMETERS
5.11 (A) Application parameters
Name
Initial
value
5 s
0 to 900 s
9999
0 to 50%
9999
9999
0 to 360 s
9999
15 s
0 to 3600 s
0 h
0 to 1000 h
9999
0 to 100%
9999
0 s
0 to 360 s
0 s
0 to 360 s
9999
0 to 3600 s
9999
9999
0 to 120 Hz
9999
9999
0 to 900 s
9999
0 s
0 to 900 s
9999
0 to 50%
9999
5%
0 to 50%
0%
0 to 100%
1000%
900 to
1100%
1000%
900 to
1100%
9999
1
2
3
9999
20%
0 to 100%
9999
0 to 100%
9999
5%
0 to 100%
0
0
1
Setting
range
Set the time from when the deviation falls within the PID output hold
range until the PID output is held.
Set the range in which the PID output is held.
The PID output holding is disabled.
Set the time from when the priming operation starts until the main pump
starts.
The PID priming pump function is disabled.
Set the stirring time.
Set the interval time for the stirring operation.
Increase the set point before the PID output suspension function is
activated.
The PID sleep boost function is disabled.
Set the waiting time for the sleep boost operation.
Set the time from when the deviation reaches the output interruption
cancel level until the output is started.
Set the deceleration time for the check valve deceleration function.
The check valve deceleration function is disabled.
Set the frequency at which the check valve deceleration stops.
The check valve deceleration function is disabled.
Set the time from when the measured value reaches the lower limit pre-
warning level (Pr.1371) until the set point change is started.
As set in Pr.1370.
Set the time from when the measured value reaches the pre-warning
level (Pr.1371) until the set point change is started.
Set the operation range for the PID upper/lower limit pre-warning
function.
The PID upper/lower limit pre-warning function is disabled.
Set the set point change amount for the PID upper/lower limit pre-
warning operation.
Set the set point change rate for the PID upper/lower limit pre-warning
operation.
Set the deviation level for operating the auxiliary pressure pump.
Set the deviation level for stopping the auxiliary pressure pump.
Terminal 1 pressure input
Terminal 2 pressure input
Terminal 4 pressure input
The PID input pressure control function is disabled.
Set the input pressure warning level.
Set the input pressure fault level.
The input pressure fault detection is disabled.
Set the set point change amount when the pressure reaches the input
pressure warning level.
The protective function (E.PID) for the input pressure fault is activated.
A deceleration stop is performed when the input pressure fault occurs.
Description