 How to wire RS-485 terminals
• 1 inverter and 1 computer with RS-485 terminals
• Multiple inverters and 1 computer with RS-485 terminals
Computer
RDA
RDB
SDA
SDB
RSA
RSB
CSA
CSB
SG
FG
*1
Make connection in accordance with the Instruction Manual of the computer to be used with. Fully check the terminal numbers of the computer
since they vary with the model.
*2
For the inverter farthest from the computer, set the terminating resistor switch to ON (100 W side).
NOTE
• For branching, connect the wires as shown below.
VCC
To computer ground
To computer receive
To computer send
• To connect multiple inverters using RS-485 distributors, refer to the following. Commercially available products (as of
October 2020)
Product name
RS-485 distributor
BMJ-8-28N (Pins No. 2 and No. 8 are not connected internally.)
(A plug with a terminating resistor is not used.)
DMDH-3PN (Pins No. 2 and No. 8 are not connected internally.)
DMDH-10PN (Pins No. 2 and No. 8 are not connected internally.)
Computer
RDA
RDB
SDA
SDB
RSA
RSB
∗1
CSA
CSB
SG
FG
∗1
SG
SG
Station 0
TXD RXD
VCC
Model
∗2
SG
SG
SG
Station 1
TXD RXD
To receiving terminal
of the next inverter
To sending terminal
of the next inverter
To next inverter
To earth (ground)
terminal
Manufacturer
HACHIKO ELECTRIC CO., LTD.
Diatrend Corp.
5.12 (N) Operation via communication and its settings
∗2
SG
Station n
477