5.11.12 Automatic restart after instantaneous power failure/flying
start with an induction motor
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
The inverter can be restarted without stopping the motor in the following conditions:
• When switching from commercial power supply operation over to inverter running
• When an instantaneous power failure occurs during inverter running
• When the motor is coasting at start
Pr.
162
Automatic restart after
A700
instantaneous power failure
selection
299
Rotation direction detection
A701
selection at restarting
57
Restart coasting time
A702
58
Restart cushion time
A703
163
First cushion time for restart 0 s
A704
164
First cushion voltage for
A705
restart
165
Stall prevention operation
A710
level for restart
611
Acceleration time at a restart 9999
F003
*1
The coasting time when Pr.57 = "0" is as shown below. (When Pr.162, Pr.570 are set to the initial value.)
FR-F860-00027: 0.5 s
FR-F860-00061 and FR-F860-00090: 1.0 s
FR-F860-00170 to 00680: 3.0 s
FR-F860-01080 or higher: 5.0 s
*2
The same operation is performed for the both settings.
448
5. PARAMETERS
5.11 (A) Application parameters
Name
Initial value
0
9999
9999
1 s
0%
110%
Setting
range
Frequency search only performed at the first start
*2
0 (2)
, 1000
*2
(1002)
1, 1001
Reduced voltage start only at the first start
(no frequency search)
3, 1003
Frequency search only performed at the first start (reduced
impact restart)
Frequency search at every start
*2
10 (12)
,
*2
1010 (1012)
11, 1011
Reduced voltage start at every start (no frequency search)
13, 1013
Frequency search at every start (reduced impact restart)
0
Without rotation direction
1
With rotation direction
9999
When Pr.78 = "0", with rotation direction
When Pr.78 = "1, 2" without rotation direction
0
Coasting time differs according to the inverter capacity.
0.1 to 30 s
Set the time delay for the inverter to perform a restart after
restoring power due to an instantaneous power failure.
9999
No restart
0 to 60 s
Set the voltage cushion time for restart.
0 to 20 s
Set the voltage cushion time for restart.
Consider this matched to the size of the load (moment of
inertia/torque)
0 to 100%
0 to 400%
Set the stall prevention operation level at a restart operation on
the assumption that the inverter rated current is 100%.
0 to 3600 s
Set the acceleration time that takes to reach Pr.20
Acceleration/deceleration reference frequency setting at a
restart.
9999
Standard acceleration time (for example, Pr.7) is applied as
the acceleration time at restart.
Description