5.7.14
Motor overspeeding detection
PM
PM
PM
The Overspeed occurrence (E.OS) is activated when the motor speed exceeds the overspeed detection level. This function
prevents the motor from accidentally speeding over the specified value, due to an error in parameter setting, etc.
Pr.
374
Overspeed detection level
H800
*1
The maximum motor frequency is set in Pr.702 Maximum motor frequency. When Pr.702 = "9999" (initial value), the Pr.84 Rated motor
frequency setting is applied as the maximum motor frequency.
Motor speed
Pr.374
ALM
270
5. PARAMETERS
5.7 (H) Protective function parameter
Name
Initial value
9999
Coast to stop
Time
ON
E.OS
Setting
range
0 to 590 Hz
If the motor rotation speed exceeds the speed set in Pr.374
during PM motor control, Overspeed occurrence (E.OS)
occurs, and the inverter output is shut off.
9999
During PM motor control, E.OS occurs when the speed
exceeds the "maximum motor frequency + 10 Hz".
Description
*1

Advertisement

Table of Contents