Mitsubishi Electric 800 Series Instruction Manual page 524

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Object
Object name
identifier
25
Cumulative power
52
PID set point
54
PID deviation
67
PID measured value 2
92
Second PID set point
94
Second PID deviation
95
Second PID measured
value 2
200
Alarm history 1
201
Alarm history 2
202
Alarm history 3
203
Alarm history 4
300
*2
Speed scale
310
PID set point CMD
311
PID measured value
*2
CMD
312
PID deviation CMD
320
Second PID set point
CMD
321
Second PID measured
value CMD
322
Second PID deviation
CMD
398
Mailbox parameter
399
Mailbox value
10007
Acceleration time
10008
Deceleration time
*1
R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array, even when "Write Access Denied" is returned
due to inconsistency of the writing requirements such as the operating mode, on condition that the values are written within the setting range.
*2
If communication speed command source is other than NET, the setting value can be written, but not to be applied.
*3
When both Pr.1136 and Pr.1138 ≠ "9999", the setting range is from the smaller coefficient to the larger coefficient of Pr.1136 and Pr.1138.
Depending on the setting, the writing value and the reading value may not be the same at the minimum digit.
Present value
*1
access type
R
Represents the cumulative power monitor.
R
Represents the PID set point monitor.
R
Represents the PID deviation monitor.
(Minus display is available with reference to 0%, in 0.1%
increment.)
R
Represents the PID measured value 2 monitor.
R
Represents the second PID set point monitor.
R
Represents the second PID deviation monitor.
(Minus display is available with reference to 0%, in 0.1%
increment.)
R
Represents the second PID measured value 2 monitor.
R
Represents the fault history 1 (the latest fault) monitor.
R
Represents the fault history 2 (second fault in past) monitor.
R
Represents the fault history 3 (third fault in past) monitor.
R
Represents the fault history 4 (fourth fault in past) monitor.
C
Controls the ratio of the frequency command. (Setting range:
0.00 to 100.00)
(Refer to
C
Set the PID action set point.
*2
This object is the set point during PID operation if Pr.128 =
"60 or 61". (Setting range: 0.00 to 100.00)
C
Set the PID measured value.
This object is the measured value during PID operation if
Pr.128 = "60 or 61". (Setting range: 0.00 to 100.00)
C
Set the PID deviation. (0.01 increment)
*2
This object is the deviation during PID operation if Pr.128 =
"50 or 51". (Setting range: -100.00 to 100.00)
C
Set the second PID action set point.
This object is the set point during PID operation if Pr.753 =
"60 or 61". (Setting range: 0.00 to 100.00)
C
Set the second PID measured value.
This object is the measured value during PID operation if
Pr.753 = "60 or 61". (Setting range: 0.00 to 100.00)
C
Set the second PID deviation. (0.01 increment)
This object is the deviation during PID operation if Pr.753 =
"50 or 51". (Setting range: -100.00 to 100.00)
W
Access to the properties which are not defined as objects are
available. (Refer to
W
W
Set Pr.7 Acceleration time.
W
Set Pr.8 Deceleration time.
Description
page
518.)
page
526.)
5.12 (N) Operation via communication and its settings
Unit
kilowatt-
hours
(19)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
no-units
(95)
percent
(98)
no-units
(95)
*3
no-units
(95)
*3
percent
(98)
no-units
(95)
*3
no-units
(95)
*3
percent
(98)
no-units
(95)
no-units
(95)
seconds
(73)
seconds
(73)
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10
523

Advertisement

Table of Contents
loading

Table of Contents