 32-bit data
No.
H0200
reserved
H0201
Output frequency (0-15bit)
H0202
Output frequency (16-31bit)
H0203
Setting frequency (0-15bit)
H0204
Setting frequency (16-31bit)
H0205
Motor rotation (0-15bit)
H0206
Motor rotation (16-31bit)
H0207
Load meter (0-15bit)
H0208
Load meter (16-31bit)
H0209,
reserved
H020A
H020B
Watt-hour meter (1kWh step) (0-15bit)
H020C
Watt-hour meter (1kWh step) (16-31bit)
H020D
Watt-hour meter (0.1/0.01kWh step) (0-15bit)
H020E
Watt-hour meter(0.1/0.01kWh step) (16-31bit)
H020F to
reserved
H03FF
 Waiting time for the communication line error output after a
communication error
Waiting time for the communication error output after a communication line error occurrence can be set.
Pr.
500
Communication error execution waiting time
Communication line status
When a communication line error occurs and lasts longer than the time set in Pr.500, it is recognized as a communication error.
If the communication returns to normal within the time, it is not recognized as a communication error, and the operation
continues.
NOTE
• The communication option error (E. 1) is not included in the targets of Pr.500.
• Operations at communication error occurrences can be selected with Pr.502 Stop mode selection at communication
error. (Refer to
page
640
9. APPENDIX
9.3 For customers using HMS network options
Description
Name
Normal
Communication error
(E.OP1)
Alarm signal(LF)
(Pr.502 = 3)
479)
Unit
-
-
0.01 Hz
signed
0.01 Hz
unsigned
1 r/min
signed
0.1%
unsigned
-
-
1 kWh
unsigned
0.1/0.01 kWh
unsigned
-
-
Setting range
0 to 999.8 s
Normal
Error
Pr.500
setting time
setting time
Type
Read/write
-
R
R
R
R
-
R
R
-
Minimum setting
Initial value
increments
0.1 s
0 s
Error
Recognition
Pr.500
ON