Step 11 Configure the TPM.
----End

7.25 Removing the DVD Drive

Remove the DVD drive before replacing it with a new one.
With Eight 2.5-inch Hard Disks
Step 1 Wear an ESD wrist strap. For details, see
Step 2 Determine the cabinet number and chassis number of the server, and label its
panel to prevent misoperations.
Step 3 Power off the RH2288H V3. For details, see
Step 4 Remove all external cables such as power and network cables.
Step 5 Remove the RH2288H V3 and put it on an ESD desktop. For details, see
Removing the
Step 6 Remove the chassis cover. For details, see
Step 7 Remove the air duct. For details, see
Step 8 Remove all fan modules. For details, see
Step 9 Press and hold down the latches on both sides of a fan module bracket, and lift
the bracket. Use the same method to lift the other fan module bracket. See steps
(1) and (2) in
Issue 46 (2022-12-28)
NO TE
If the TPM 2.0 is installed and the TXT function is enabled, but the TPM 2.0 status on the
BIOS is unknown, contact technical support.
If a spare TPM is installed:
a.
Set the TPM configuration items on the BIOS to ensure that the TPM
settings are the same as the recorded TPM settings. For details, see the
Huawei Server Grantley Platform BIOS Parameter Reference
b.
Restore the backup data on the spare TPM to overwrite its factory
settings.
If the removed TPM is installed:
a.
Check whether the BIOS version of the mainboard where the TPM is
located is earlier than that before the removal.
If yes, upgrade the BIOS version to ensure that the BIOS version of
the mainboard where the TPM is located is not earlier than that
before the removal. For details, see the
Server Upgrade Guide
If no, go to
b.
Set the TPM configuration items on the BIOS to ensure that the TPM
settings are the same as the recorded TPM settings. For details, see the
Huawei Server Grantley Platform BIOS Parameter Reference
Server.
Figure
7-47.
Copyright © Huawei Technologies Co., Ltd.
.
Step
11.b.
1 Safety
4.2 Powering Off the
7.11 Removing the Chassis
7.13 Removing the Air
7.15 Removing a Fan
7 Replacing Parts
FusionServer Pro Rack
Instructions.
Server.
Duct.
Module.
.
.
3.6
Cover.
190

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r003

Table of Contents