Maintenance And Service; Led Indicators; Communication Settings; Ip Query - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa tcp bridge
Table of Contents

Advertisement

1MRS756019
8.
8.1.
Table 8.1.-1

LED indicators

LED
Color
Power
Green
Link LAN
Green
RX LAN
Green
TX LAN
Green
RX SPA
Green
TX SPA
Green
DIAG
Green
8.2.
8.3.
Ethernet Adapter
SPA/TCP Bridge
Installation and Commissioning Manual

Maintenance and service

If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service
operation is to replace the entire module.
LED indicators
State
On
On
On
On
On
On
Red
Off
On
Flashing
On
On
On
Flashing
Off
On
Off
Off
Flashing
Possible sequences are:
1 → 3 → 5
1 → 2
1 → 3 → 4
1 → 3 → 6

Communication settings

The following IED-specific settings have to be checked when setting up
REF 541/3/5, REM 543/5 or RET 541/3/5:
SPA baud rate and SPA slave number in IED
*
Baud rate and slave number have to be according to the SPA-ZC 402 configuration
in X3.2/Communication 2.

IP Query

By using the IP Query Tool in Communication Engineering Tool (CET) for SPA-ZC
40x, it is possible to see all connected SPA-ZC 40x, devices, their communication
parameters and version information.
Example:
Sending IP query 1
RECEIVED MESSAGE FROM 10.58.125.151:
Mac Address: 00-0C-02-B0-04-89
Subnet Mask: 255.255.255.0
Default Gateway: 10.58.125.150
Sequence
number
1
2
3
4
5
6
Normal situation
Missing boot image
Configuration file is missing
Configuration error
SPA-ZC 402
SPA-ZC 402
Description
Power on
Indication for LAN link OK
Indication for incoming LAN traffic
Indication for outgoing LAN traffic
Indication for incoming SPA traffic
Indication for outgoing SPA traffic
Bootloader booting
Bootloader, missing boot image
Starting
OK, missing configuration
OK, configuration in use
Configuration error
39