Maintenance And Service; General About Service; Led Indicators; Spa-Zc 402 Communication Settings - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ ethernet adapter
Table of Contents

Advertisement

1MRS755380
6.
6.1.
6.2.
Table 6.2.-1

LED indicators

LED
Color
Power
Green
Link LAN
Green
RX LAN
Green
TX LAN
Green
RX SPA
Green
TX SPA
Green
DIAG
Green
Red
6.3.
SPA/ Ethernet Adapter
Installation and Commissioning Manual

Maintenance and service

General about service

If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service
operation is to replace the entire module. For more details, refer to the ordering
information.
LED indicators
State
On
On
On
On
On
On
Off
On
Flashing
On
On
On
Flashing
Off
On
Off
Off
Flashing
Possible sequences are:
1
3
5
Normal situation
1
2
Missing boot image
1
3
4
Configuration file is missing
1
3
6
Unrecoverable error situation

SPA-ZC 402 communication settings

SPA addresses in sAddr are not properly configured if
• diagnostic counter SPAReplyTimo increases constantly and SPAReplyData
remains 0
• quality of the data is INVALID
The following protocol specific settings have to be checked when setting up IED:
• SPA baud rate and SPA slave number
The baud rate and slave number have to be according to the SPA-ZC 402
configuration.
Sequence number Description
Power on
Indication for LAN link OK
Indication for incoming LAN traffic
Indication for outgoing LAN traffic
Indication for incoming SPA traffic
Indication for outgoing SPA traffic
1
Bootloader booting
2
Bootloader, missing boot image
3
Starting
4
OK, missing configuration
5
Everything OK
6
Unrecoverable error situation
SPA-ZC 402
57