Maintenance And Service; Led Indicators; Communication Settings - ABB SPA-ZC 400 Installation And Commissioning Manual

Ethernet adapter modbus/tcp brigde
Table of Contents

Advertisement

1MRS756014
8.
8.1.
Table 8.1.-1

LED indicators

LED
Color
Power
Green
Link LAN
Green
RX
LAN
Green
TX
LAN
Green
DIAG
Green
Red
RX
Green
8.2.
Ethernet Adapter
Modbus/TCP Brigde
Installation and Commissioning Manual

Maintenance and service

If the SPA-ZC 400 module or a part of it is found to be faulty, the normal
service operation is to replace the entire module. For more details, refer to
Table 9.-1.
LED indicators
State
On
On
On
On
Off
On
Flashing
On
On
On
Flashing
Off
On
Off
Off
Flashing
On
Possible sequences are:
1 → 3 → 5
Normal situation
1 → 2
Missing boot image
1 → 3 → 4
Configuration file is missing
1 → 3 → 6
Configuration error
If configuration error is detected because of the mismatches in
downloaded the CID file, download a simpler configuration.
Check also the log file in SPA-ZC 400.

Communication settings

REF 541/3/5, REM 543/5 and RET 541/3/5 addresses or baud rates are not
properly defined if:
Diagnostic counter SPAReplyTimo increases constantly and
*
SPAReplyData remains 0 in the LDO.LLNO.ComDiag data object.
These diagnostic counters are readable from the IEC 61850 client.
Quality of the data is INVALID.
*
Sequence
Description
number
Power on
Indication for LAN link OK
Indication for incoming LAN traffic
Indication for outgoing LAN traffic
1
Bootloader booting
2
Bootloader, missing boot image
3
Starting
4
OK, missing configuration
5
OK, configuration in use
6
Configuration error
Indication for incoming LON traffic
(LON and SPA)
SPA-ZC 400
41

Advertisement

Table of Contents
loading

Table of Contents