Maintenance And Service; Led Indicators; Communication Settings - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa/ethernet adapter spa to iec 61850 gateway
Table of Contents

Advertisement

1MRS755380
9.
9.1.
Table 9.1.-1

LED indicators

LED
Color
Power
Green
Link LAN
Green
RX LAN
Green
TX LAN
Green
RX SPA
Green
TX SPA
Green
DIAG
Green
9.2.
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

Maintenance and service

If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service
operation is to replace the entire module.
For more details, refer to Section 13. Ordering information.
LED indicators
State
On
On
On
On
On
On
Red
Off
On
Flashing
On
On
On
Flashing
Off
On
Off
Off
Flashing
Possible sequences are:
1 → 3 → 5
1 → 2
1 → 3 → 4
1 → 3 → 6
If configuration error is detected because of the mismatches in
downloaded the CID file, download a simpler configuration. Check
also the log file in SPA-ZC 402.

Communication settings

SPA addresses in sAddr are not properly defined if
Diagnostic counter SPAReplyTimo increases constantly and SPAReplyData
*
remains 0 in the LD0.CDGGIO1 logical node. These diagnostic counters are
readable from the IEC 61850 client.
Quality of the data is INVALID.
*
Sequence
number
1
2
3
4
5
6
Normal situation
Missing boot image
Configuration file is missing
Configuration error
SPA-ZC 402
SPA-ZC 402
Description
Power on
Indication for LAN link OK
Indication for incoming LAN traffic
Indication for outgoing LAN traffic
Indication for incoming SPA traffic
Indication for outgoing SPA traffic
Bootloader booting
Bootloader, missing boot image
Starting
OK, missing configuration
OK, configuration in use
Configuration error
63

Advertisement

Table of Contents
loading