10

Technical data

Further information about the product and accessories is found at:
new.abb.com/low-voltage/products/safety-products
Stated technical data apply when power supply voltage is +24 VDC and ambient temperature
is +25 °C, unless stated otherwise.
Manufacturer
Address
Order code/Ordering data
Power supply
Required power supply type
Operating voltage
Total current consumption
Note: Total current consumption is the supply current when there is no information
output current, no current on Tina 3 Aps power output. Valid over the operating voltage
and ambient temperature range.
DYNlink signal
DYNlink Input signal voltage
DYNlink Output signal voltage
Note: The purpose of stating the voltage in RMS is to facilitate the measurement of the
square-wave DYNlink signal with a multimeter.
Time delay between DYNlink
input and output signal (T
Information output
Output voltage high
Output current
Safety loop output
Current through safety device
contacts
Short circuit current between
contacts
Loop resistance
2TLC172125M0201 Rev.F
ABB Electrification Sweden AB
SE-721 61 Västerås
Sweden
2TLA020054R0200: Tina 3A Adapter 2 contacts M12-5
2TLA020054R1400: Tina 3Aps Adapter 2 contacts +
supply M12-5
PELV/SELV, not intended to be connected to a DC
distribution network.
Note: A DC distribution network is defined in
IEC 61326-3-1:2017 as "Local DC electricity supply
network in the infrastructure of a certain site or
building intended for connection of any type of
equipment".
+24 VDC +15 %, -25 %
Maximum: 35 mA
Minimum: 8 V
Maximum: 15 V
Minimum: 8 V
Maximum: 15 V
Maximum: 70 µs
)
DELAY
Nominal: Operating voltage - 2 VDC
low
Maximum: 2 VDC
Maximum: 10 mA
Closed, nominal: 2 mA
Wetting, nominal: 12 mA for 700 µs after closing
contact
Nominal: 12 mA
Closed, maximum: 500 Ω
Open, minimum: 20 kΩ
RMS
RMS
RMS
RMS
RMS
RMS