SPA-ZC 402
4.5.3.
38
SPA/ Ethernet Adapter
Installation and Commissioning Manual
When the actual IEC 61850 data model is created the logical device name has two
parts:
• Device Object name
• Logical Device name
for example SPAZC40xLD0.

Importing IEC 61850 data object model of IED

1. Right-click to select a Logical Device object (for example REX 521).
2. Import the data model by selecting the Generate Configuration function and by
choosing the right IED type.
CET builds the IED's IEC 61850 data model from the selected Connectivity
Package to the Project Explorer dialog under the selected logical device.
The tool imports default data sets and report control blocks (RCB) to logical device
LD0, see Fig. 4.5.3.-1. Data sets include a set of selected data attributes from IED's
IEC 61850 data model. These data sets are used in the IEC 61850-8-1 event
reporting model. If data attributes are selected to the data set and the same data set
is used in report control block (RCB), the data set generates a spontaneous event
which will be sent to the IEC 61850 client. If the data set is not defined in the RCB,
IEC 61850-8-1 reads the data separately. You can modify data sets with Dataset
Editor, see Section 4.9. Using Dataset Editor.
1MRS755380