Electrical connection
6.5.1.

Terminal compartment: open

38
SAEx 16.2-UW / SAREx 07.2-UW
Figure 38: Open terminal compartment
[1]
Cover (illustration shows type of protection Ex e)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Connection frame
Electric shock due to presence of hazardous voltage!
Death or serious injury.
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
Information: Terminal compartment is designed either in type of protection Ex
e (increased safety) or in type of protection Ex d (flameproof enclosure) (refer
to Ex marking on name plate). The flameproof interior of the connected device
remains closed when removing the cover [1].
2.
Insert cable glands suitable for connecting cables.
Information: When selecting cable glands observe type of protection (with Ex e
or Ex d approval) and enclosure protection IP (refer to name plate).
The type of protection stated on the name plate IP is only ensured if suitable
cable glands are used.
Figure 39: Name plate, example with enclosure protection IP68
Information: For shielded cables: Use EMC cable glands.
3.
Seal unused cable entries with approved plugs suitable for the required protec-
tion type.