Test Run - AUMA SAEx 07.2-UW Operation Instructions Manual

Multi-turn actuators
Table of Contents

Advertisement

SAEx 07.2-UW
SAEx 16.2-UW / SAREx 07.2-UW
ACExC 01.2 Non-Intrusive Profibus DP
Set end position OPEN
CMD0010 with hand-
wheel)
Set end position OPEN
CMD0010 (without hand-
wheel)
Confirm new end posi-
tion
Information
10.4.

Test run

12. Make selection:
Edit → back to step 9: Set end position CLOSED "once again"
Esc → back to step 4; either set end position OPEN or exit the menu.
13. Re-set end position OPEN:
Information: The following description applies to actuators with handwheel.
For actuators without handwheel, continue with the next step.
13.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
13.2 Engage manual operation.
13.3 Turn handwheel until valve is open.
13.4 Turn handwheel by approximately half a turn (overrun) in the opposite
direction of end position.
13.5 Set selector switch to position 0 (OFF).
Display indicates: Set end pos. OPEN? Yes No
14. Re-set end position OPEN:
Information: The following description applies to actuators without handwheel.
For actuators with handwheel, continue with the next step.
14.1 Set selector switch in position Local control (LOCAL) and operate actu-
ator in via push button
Information: To avoid valve damage, set the torque switching to a value
as low as possible!
14.2 Operate a small distance (in push-to-run operation via push button
(CLOSE)) out of end position CLOSED to consider overrun.
14.3 Set selector switch to position 0 (OFF).
Display indicates: Set end pos. OPEN? Yes No
15. Press
Yes to confirm new end position.
Display indicates: End pos. OPEN set!
The right LED is illuminated (standard version) and thus indicates that the end
position OPEN setting is complete.
16. Make selection:
Edit → back to step 12: Set end position OPEN "once again"
Esc → back to step 4; either set end position CLOSED or exit the menu.
17. After setting the limit switching, reset the torque switching to the value recom-
mended by the valve manufacturer.
If an end position cannot be set: Check the type of control unit in actuator.
Only perform test run only once all settings previously described have been
performed.
SAREx 16.2-UW Control unit: electronic (MWG)
(OPEN) to the end position.
Commissioning (basic settings)
(OPEN) in
63