Electrical connection
6.4.

KP/KPH electrical connection

Short description
Technical data
32
SAEx 16.2-UW / SAREx 07.2-UW
Figure 31: KP and KPH electrical connection
[1]
Screw-type terminals
[2]
Plug-in frame (flameproof)
KP/KPH plug-in electrical connection with screw-type terminals for power and control
contacts.
KP version (standard) with three cable entries. KPH version (enlarged) with additional
cable entries. Cable entries via the cover.
The terminal compartment (with screw-type terminals) is designed in protection type
Ex e (increased safety). Plug-in connection is made via the frame. Removing the
cover is sufficient for connecting the cables. The flameproof frame remains connected
to the device. The flameproof interior of the connected device remains sealed.
Table 16:
KP/KPH electrical connection
No. of contacts max.
Designations
Connection voltage max.
Rated current max.
Type of customer connection
Connection diameter max.
SAREx 16.2-UW Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
Power contacts
Control contacts
3 + protective earth conduct-
38 pins/sockets + protective earth con-
or (PE)
ductor (PE)
1 to 24, 31 to 40, 47 to 50, PE
U1, V1, W1,
(PE)
525 V
250 V
25 A
10 A
Screw connection
Screw connection
2
6 mm
1.5 mm
2