SAEx 07.2-UW
SAEx 16.2-UW / SAREx 07.2-UW
ACExC 01.2 Non-Intrusive Profibus DP
6.3.

KT/KM electrical connection

Short description
Technical data
Figure 20: KT/KM electrical connection
[1]
Terminal carrier with screw-type/spring clamp terminals
[2]
Connection frame
Figure shows KT version
KT plug-in electrical connection with screw-type terminals for power connection and
spring clamp terminals for control contacts.
KM version with additional support terminals (terminal blocks) via terminal carrier.
When using solid fieldbus cables in line topology, imperatively use support terminals.
Both versions (KT and KM) are available with terminal compartment in protection
type Ex e (increased safety) as well as in protection type Ex d (flameproof enclosure)
(refer to Ex marking on name plate).
Plug-in connection is made via the connection frame. For cable connection, simply
remove the cover. The connection frame with the cable entries remains within the
device. The flameproof interior of the connected devices remains sealed.
Table 14:
KT/KM/KL electrical connection
No. of contacts max.
Designations
Support terminals max.
Connection voltage max.
Rated current max.
Type of customer connection
Connection diameter max.
1)
Four protective earth connections within frame
2)
The sum of the currents of all control contacts must not exceed 50 A.
SAREx 16.2-UW Control unit: electronic (MWG)
Power contacts
1)
6 + PE conductors
U1, V1, W1, U2, V2, W2,
3
1,000 V
25 A
Screw connection
PE = Ring lug/U-bracket
2
10 mm
Electrical connection
Control contacts
50
1 to 36, 37 to 50
12
250 V
2)
5 A
Spring clamp terminals
2
2.5 mm
25