Terminal Compartment: Close - AUMA SAEx 07.2-UW Operation Instructions Manual

Multi-turn actuators
Table of Contents

Advertisement

SAEx 07.2-UW
Electrical connection
6.4.4.

Terminal compartment: close

36
SAEx 16.2-UW / SAREx 07.2-UW
Figure 36: Close terminal compartment
[1]
Cover (figure shows KP version)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland
[6]
Flameproof frame
1.
Clean sealing faces of cover [1] and frame [6].
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4.
Fit cover [1] and fasten screws [2] evenly crosswise.
5.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
SAREx 16.2-UW Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP