SAEx 07.2-UW
Electrical connection
24
SAEx 16.2-UW / SAREx 07.2-UW
For LSW 82 cable set, the cover must be opened at wall bracket level and the
cables must be connected to the terminals according to the terminal plan.
Connect flexible cables using wire end sleeves.
Figure 18: Connection using LSW 82
[1]
Cover for electrical connection on wall bracket
[2]
Terminals
[3]
Cables (for flexible cables with wire end sleeves)
-
When connecting, make sure that the shield of both connecting cables is
sufficiently overlapping (approx. 2 mm over the O-ring) the contact socket
of the cable gland.
-
Connect all protective earth wires to the protective earthing (symbol
When installing the connecting cables, make sure not to fall short of the minimum
bending radius.
Figure 19: Example at actuator plug/socket connector
Table 13:
Connecting cable
Motor cable
Hybrid cable
SAREx 16.2-UW Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
Outer diameter
(d) [mm]
approx. 12.1
approx. 17.2
).
Minimum bending radius
r [mm]
90
105