AUMA SAEx 07.2-UW Operation Instructions Manual page 62

Multi-turn actuators
Table of Contents

Advertisement

SAEx 07.2-UW
Commissioning (basic settings)
Set end position
CLOSED CMD0009with
handwheel)
Set end position
CLOSED CMD0009
(without handwheel)
Confirm new end posi-
tion
62
SAEx 16.2-UW / SAREx 07.2-UW
9.
Set end position CLOSED again :
Information: The following description applies to actuators with handwheel.
For actuators without handwheel, continue with the next step.
9.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
9.2 Engage manual operation.
9.3 Turn handwheel until valve is closed.
9.4 Turn handwheel by approximately half a turn (overrun) in the opposite
direction of end position.
9.5 Set selector switch to position 0 (OFF).
Display indicates: Set end pos.CLOSED? Yes No
10. Set end position CLOSED again :
Information: The following description applies to actuators without handwheel.
For actuators with handwheel, continue with the next step.
10.1 Set selector switch in position Local control (LOCAL) and operate actu-
ator in via push button
Information: To avoid valve damage, set the torque switching to a value
as low as possible!
10.2 Operate a small distance (in push-to-run operation via push button
(OPEN)) out of end position CLOSED to consider overrun.
10.3 Set selector switch to position 0 (OFF).
Display indicates: Set end pos.CLOSED? Yes No
11. Press
Yes to confirm new end position.
Display indicates: End pos. CLOSED set!
The left LED is illuminated (standard version) and thus indicates that the end
position CLOSED setting is complete.
SAREx 16.2-UW Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profibus DP
(CLOSE) to the end position.
(CLOSE) in

Advertisement

Table of Contents
loading

Table of Contents