Configuring A Goose Publisher; Creating A Goose Data Set - ABB eVD4 Engineering Manual

Breaker integrated protection rbx615
Table of Contents

Advertisement

1MRS757255 B
5.3.4
5.3.4.1
Breaker Integrated Protection RBX615
Engineering Guide
If the substation includes third party IEDs which need to be
configured for horizontal GOOSE communication, the SCL files
holding the information from those IEDs must be imported as well.
The third party IEDs have separate tools for creating the ICD/CID/
SCD file.

Configuring a GOOSE publisher

To control the GOOSE data publishing, such as addressing, every publisher IED
must have at least one data set for GOOSE data and one GOOSE control block.
1.
Group the data to a data set sent to IEC 61850 station bus.
2.
Define the GOOSE control block.
A 615 series IED can send single binary, double binary, integer and
floating point data values with a quality attribute. A quality
attribute is used at the receiver side to check data validity.

Creating a GOOSE data set

Define the sending data set used by the GOOSE control block. With the 615 series
IEDs, the sending GOOSE data set can have at maximum 20 data attributes to
minimize the message handling load in receiver and sending IEDs.
1.
Open the Project Navigator and browse to the IED Section submenu.
2.
Select the IED to be configured.
In the IED data model, select LLN0 logical node under LD0 logical device.
3.
In the IEC 61850 Data Engineering window on the right, select the Data
Set Engineering tab.
Section 5
GOOSE
25

Advertisement

Table of Contents
loading

Table of Contents