Section 2
Engineering tool set
A PC with PCM600 can be connected to any 650 series IED within a station using the Ethernet
connection.
The Ethernet connection can then later also be used for service and maintenance purposes. The
connection is also used to handle disturbance records in COMTRADE format from protection IEDs
using the IEC 61850 file transfer.
The IEDs of today are designed on the concept of the IEC 61850 standard. This is mainly given for
the organization of functions represented by an equivalent logical node in the IEC 61850 standard.
The mapping between the logical node data model in the IED, following the structure and rules in
part 7 of the IEC 61850 standard, and the function blocks in an IED configuration is given in the IEC
61850 communication protocol manual.
The concept is also used for DNP3 protocol. The signals used or delivered by a function block are
automatically generated and available for station communication. This concept allows a very
efficient cost saving signal engineering.
The IEC 60870-5-103 protocol is engineered in Application Configuration tool and Parameter
Setting tool.
The engineering of the used communication protocols is a separate task and an addition to the
engineering of protection and control functions.
PCM600 can be used for different purposes throughout the IED life cycle. A set of special tools is
available for different applications.
The applications can be organized in:
IED product engineering
IED communication engineering per protocol
IED system monitoring
IED product diagnostic
This manual is valid for PCM600 supporting the 650 series product.
2.2

IED engineering process

PCM600 is used for various tasks in the IED engineering process. See
IED engineering management
Communication engineering
16
Organizing the bay IEDs in the structure of the substation by defining voltage levels and
bays below the substation. PCM600 manages the project.
Configuring the IED functions (for example protection and control functions and LHMI
functions) by using the Application Configuration tool.
Configuring the parameters and setting values for the IED itself and for the process
functionality by using the Parameter Setting tool.
Drawing single line diagrams and do the link to dynamic process values by using the
Graphical Display Editor tool. The single line diagrams are shown on the LHMI on the bay
IED.
Configuring connections between the application configuration function blocks and
physical hardware input and outputs by using the Signal Matrix tool or the Application
Configuration tool.
© Copyright 2011 ABB. All rights reserved
1MRK 511 245-UUS A
SEMOD58260-4 v5
Figure
3:
650 series
Engineering manual

Advertisement

Table of Contents
loading