Figure 5:
The following description is an example valid for standard PCs using Microsoft Windows operating
system. The example is taken from a Laptop with one Ethernet interface.
When a computer is connected to the IED and the setting
local HMI path Main menu/Configuration/Communication/TCP-IP configuration/1:ETHFRNT/
DHCPServer, the IEDs DHCP server for the front port assigns an IP address for the computer. The
computer must be configured to obtain its IP address automatically as described in the following
procedure.
1.
Select Network Connections in the PC.
IEC09000355 V1 EN-US
Figure 6:
2.
Select Properties in the status window.
650 series
Engineering manual
RJ-45
Tx
Rx
Point-to-point link between IED and PCM600 using a null-modem cable
Administrator rights are requested to change the PC communication setup. Some
PCs have the feature to automatically detect that Tx signals from the IED are
received on the Tx pin on the PC. Thus straight (standard) Ethernet cable can be
used.
Select: Network connections
© Copyright 2011 ABB. All rights reserved
PCM600
Tx
Rx
IEC09000096-1-en.vsd
DHCPServer is set to Enabled via the
IEC09000355-1-en.vsd
Section 4
Setting up a project