5.3

Connecting signals in SMT

SMT is used to do cross references, see
between physical IO signals and function blocks.
for the GOOSE engineering.
IEC08000173 V2 EN-US
Figure 39: SMT: Operation principles
A binary input channel can be connected to one or several function block inputs, see
binary input channel is connected to several different function blocks in ACT, the connection will
appear as glue logic in SMT.
A binary output channel can only be activated from one function block output. If it should be
activated from more than one function block output, glue logic has to be used. Glue logic means
inserting a logical gate (OR and AND blocks) between the function blocks and the binary output
channel. This can be engineered in SMT.
650 series
Engineering manual
BIO
BIO
TRM
IEC 61850
GOOSE Inputs
Connections made in SMT are automatically shown in ACT. Connections made in
ACT are automatically shown in SMT.
© Copyright 2011 ABB. All rights reserved
Figure
39:
FBs
FBs
SMAI
GOOSE FBs for
binary and analog
data, interlocking
communication
and voltage control
IEC08000173_2_en.vsd