Dnp3 Communication Engineering; Signal Configuration User Information; Configuring Dnp3 Protocol Signals - ABB Relion 650 Series Engineering Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 245-UUS A
Section 9
9.1

Signal configuration user information

CMT allows to configure the signals that are used to communicate with clients or master units for
DNP3 protocols.
On the left window CMT organizes all available signals from the application configuration in
containers that are preselected as signal types.
On the right window CMT provides containers that are selected by tabs. Each container represents
one communication channel. The number of possible communication channels is IED type
dependent. The IED uses TCP/IP as communication channel. DNP3 can be tunneled over TCP/IP,
and serial communication RS-485 is not supported.
Use direction icons that are located between the windows to move all signals or a set of individual
signals between the windows.
DNP3 signal types, index and default setting for classes are predefined in CMT. Adapt the signal
configuration to project definitions. The signal type can not be modified due to the fact that the
internal signal set up is fixed.
When the default configuration values are sufficient, the task is finished when all signal are moved
according to the project requirements.
With the
the default selections.
Only for analog measurements additional configuration parameters are shown to do signal scaling
to DNP3 protocol presentation. This can be done when the
Finally, the signal configuration to the different DNP3 channels can be listed in a report on demand
and per signal type.
9.2

Configuring DNP3 protocol signals

1.
Save the actual project configuration in PCM600 to make all signals visible for CMT.
650 series
Engineering manual

DNP3 communication engineering

Basic knowledge about DNP3 and the used definitions are required to use CMT. See
the DNP3 communication protocol manual for information on the DNP3
implementation in the IED.
Save option, the signals are stored for the communication part of the IED according to
Direct configured hardware channels in the application configuration (see
Figure
73) appear in CMT (see
channels to be sent by DNP3, as they are not event-handled.
© Copyright 2011 ABB. All rights reserved
Configuration Table View is selected.
Figure
74). Do not configure these hardware
Section 9
DNP3 communication engineering
GUID-AC54A350-D43E-4C0C-995C-012D7533ECC1 v2
GUID-4908ED38-733F-4A8B-AEB2-90C0CB9A5274 v2
93