Section 3
Engineering process
Setting up the PCM600 project
ACT Application configuration
PST Parameter setting and configuration
GDE Single line diagram configuration
Local HMI engineering
Communication protocol engineering
20
Build the plant structure according to the substation structure.
For performance reasons, do not insert more than 65 IEDs of 650 series
type in one PCM600 project. Larger projects can be divided into several
PCM600 projects.
Insert an IED in plant structure which can be done in many ways. By inserting the IED in
online mode where the configuration is read from the physical IED, by inserting an IED in
offline mode, by importing a *.pcmi file or by selecting an IED template from the
template library (*.pcmt).
Rename the IED objects in PCM600 to the projects definitions.
Configure the protection or control function for example for a transformer application
as requested.
Save the configuration made with ACT to make the interfaces and signals available for
other engineering tools within PCM600, for example for PST.
Check the configuration parameters of the physical IED for communication channels, CT
and VT conversion values of the transformer module, for example.
Check and adjust if needed the setting values for example for:
Presentation parameters for local HMI.
Settings for protection or control functions.
Number of setting groups.
Create a single line diagram of the switch yard.
Include measurements when needed.
Link the dynamic elements to functions created in ACT, for example a breaker object to
the switch function.
Include and engineer the function blocks for LHMI element groups with ACT.
Configure the function keys and LEDs with ACT.
Define the function key and LED behavior with PST.
The engineering steps are protocol dependent.
Use the communication management tool (CMT) for DNP3 engineering.
Use a station configuration tool, for example CCT600, for IEC 61850 engineering. See
the application manual for other protocols (IEC103).
The IED restarts automatically when writing an IED configuration where changes
have been made to, for example configuration parameters. It is not possible to
communicate with the IED during the restart.
© Copyright 2011 ABB. All rights reserved
1MRK 511 245-UUS A
650 series
Engineering manual