Writing Communication Configuration To Ied - ABB Relion 650 Series Engineering Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 7
IEC 61850 communication engineering
3.1.
3.2.
3.3.
3.4. Click
3.5.
4.
IEC09000631 V1 EN-US
Figure 71:
7.6

Writing communication configuration to IED

IEC communication depends on proper communication configuration in all IEDs that communicate
via IEC 61850. It is not possible to read the communication configuration from the IED to PCM600.
However it is possible to make a configuration change in one IED, without affecting the
communication engineering. For example, when the Application Configuration tool configuration
is changed, but no changes are done for the instantiation or deletion of functions that represent a
logical node.
When a changed configuration is written to the IED, the user is asked to update the
communication configuration.
1.
Select Yes in the Update Communication window to update the communication
configuration part in the IED.
2.
Click No in the Update Communication window to keep the communication configuration
part in the IED. Other parts of the configuration will be updated.
88
Substation Section will not import the "SSD-file" part of the SCD-file.
Ignore
Don't import ... protects the existing IEDs in case the SCD file does not match the
original configuration in PCM600.
Replace unknown ... can be used when it is known that the file includes additional IEDs
which are needed. The IED of type
of IEDs in for example the plant structure.
Ignore PCM Object Type to update the IED object(s) in PCM600 from the IED
type(s) in the SCD file, disregarding if the IED type(s) in the SCD file matches the IED
object(s) in PM600 or not.
Import when the definition has been completed. A progress window presents the
Start
import procedure.
IEC09000631-1-en.vsd
IEC 61850: SCL Import option
If no changes have been done in the communication configuration part, click No in
the Update Communication window.
© Copyright 2011 ABB. All rights reserved
Generic IEC 61850 IED is used to integrate these kinds
1MRK 511 245-UUS A
GUID-EE2F7AE2-2EA6-4F16-94F1-E9472CF6BB50 v2