1MRK 511 245-UUS A
Cycle Time can be selected to 5, 20 or 100 ms. Depending on function block type and the 650
The
series product only one, two or all three possibilities may be available.
The combination
function blocks like for example
execution orders is available. This gives the possibility to select a combination which fits to the
execution order range needed in that application part.
Application configuration cycle time and execution order organization
The application execution within the 650 series products is organized in three time classes, see
Figure
33.
IEC09000739 V1 EN-US
Figure 33: ACT: Possible MainApplication cycle times
650 series
Engineering manual
A minus sign in front of the cycle time, for example -200ms, indicates that the
application is time driven, otherwise the application is analogue data driven.
Analogue data driven applications require sample values from Analogue input
modules - in case the physical module is broken, applications are not executed.
Time driven applications are executed periodically regardless of the status of the
analogue signal processing.
Execution Order , Instance Number is predefined by ABB. Mainly for basic logic
AND , OR , a set of combinations spread over the full range of
For the same time point, faster cycle times are executed first.
A function block that is placed after a function block in the execution flow must
have the same or a higher cycle time and/or execution order. See
© Copyright 2011 ABB. All rights reserved
Section 5
Protection and control engineering
Figure
34.
49