1MRK 511 245-UUS A
IEC08000375 V2 EN-US
Figure 42: Local HMI: Placement of local HMI operation elements
Function block LEDGEN
•
Handles an external acknowledge signal as source to acknowledge the LEDs.
•
Generates an additional pulse for general purposes whenever the LEDs are acknowledged by
the operator.
•
Generates a pulse whenever a new LED signal occurs. It may be used to trigger an acoustical
alarm.
•
Handles the timer
Function block GRP1_LED1 to GRP3_LED15
•
The 15 LEDs on the right side of the LCD can indicate in total 45 alarms, warnings or other
signals to the operator. They are organized in three groups 1 to 3.
•
Each signal group belongs to one function block.
•
Each LED illuminates in one of the three colors: RED, YELLOW or GREEN.
•
The organization of flashing, acknowledgment and group selection is done directly between
the function blocks and the basic LHMI keys, the 'Multifunction' key [a] to toggle between the
three groups or the 'Clear' key [b] to acknowledge or reset the LEDs.
•
Only the programming of the signals is needed for the LEDs.
•
The operation mode of the LEDs is defined in Parameter Setting tool.
Function block FNKEYMD1 to 5
650 series
Engineering manual
tReset and tMax for the LED operation mode 'LatchedReset-S'.
© Copyright 2011 ABB. All rights reserved
Section 6
Local HMI engineering
59