ABB Relion 650 Series Engineering Manual page 73

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 245-UUS A
IEC08000123 V1 EN-US
Figure 53: GDE: Screen image with active GDE
Procedure
1.
Start GDE to open a presentation of the tool.
2.
GDE has a fixed symbol library window on the left side of the display.
3.
The presentation is empty when no page exists for the IED.
Display window and sequence order
Rules to handle HMI pages:
Several single line diagrams can be created for one bay.
The IED supports one bay.
The sequence order of the HMI pages in the Graphical Display Editor starts from left to right.
Measurements and the single line diagram can be shown on the page in any possible order
and placement.
All symbol objects, for example apparatus, text and measurement, on the HMI page must be
linked to the correct function block in the application configuration in order to present the
correct process values.
650 series
Engineering manual
HMI display
Regard the
window pages
squence of pages
Symbol library
IED HMI
window
display window
It is important to link correctly between the HMI display page and the
corresponding bay that is presented as a single line diagram on this HMI page.
© Copyright 2011 ABB. All rights reserved
Local HMI engineering
IEC08000123.vsd
Section 6
67