Importing Scl Files To Pcm600; Importing Scd Files - ABB Relion 650 Series Engineering Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 245-UUS A
4.2. Define client IEDs for each GOOSE control block.
4.3. Link the IEDs to the GOOSE control block that shall receive the GOOSE control block.
5.
Update the data flow.
6.
Export the updated SCD file.
7.5

Importing SCL files to PCM600

The IED engineering tool must be able to receive a SCD file or an ICD file as import to receive the
engineered communication extensions, for example for the different IEDs.
7.5.1

Importing SCD files

Procedure to import a SCD file to PCM600:
1.
Select the station in the plant structure.
2.
Right-click the station and select
3.
Select the file to be imported from the open standard Windows menu and start the reading.
SCL Import Options window opens, which queries how the file should be handled during
4.
A
import, see
IEC09000631 V1 EN-US
Figure 69: IEC 61850: Import SCD file
650 series
Engineering manual
Be sure to set the same GoID for sending and receiving GOOSE
messages.
Note that one data must only be included in a GOOSE data set once.
All data sets, all Report Control Blocks and GOOSE control block must be located at
LD0 / LLN0.
Import ...
Figure
69.
IEC09000631-1-en.vsd
© Copyright 2011 ABB. All rights reserved
Section 7
IEC 61850 communication engineering
GUID-DA35857B-999B-4533-8148-864B69ECDBCE v1
GUID-93604C46-1A65-4A25-9334-59478FC1C0A0 v3
85