ABB Relion 650 Series Engineering Manual page 92

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 7
IEC 61850 communication engineering
4.1.
4.2. Click
4.3. Click
4.4. Click
4.5. Start
5.
Make connections from sending IEDs to receiving function blocks in SMT.
5.1.
6.
Write the configuration to the IED, see
86
Ignore Substation Section to not import the "SSD-file" part of the SCD-file.
Click
Don't import IEDs of unknown type to protect the existing IEDs in case the SCD file
does not match the original configuration in PCM600.
Replace unknown ... can be used when it is known, that the file includes additional
IEDs that are needed. The IED of type "Generic IEC 61850 IED" is used to integrate these
kinds of IEDs in the plant structure etc.
Ignore PCM Object Type to update the IED object(s) in PCM600 from the IED
type(s) in the SCD file, disregarding if the IED type(s) in the SCD file matches the IED
object(s) in PM600 or not.
Import when the file definition has been completed. A progress window presents
the import procedure.
Make connections between the signals that the server is sending and all the GOOSE
receive interface function blocks included in the application configuration on the client's
side.
If a client is defined for GOOSE receive then at least one cross in SMT is
required to be able to write the configuration to the IED.
Be sure to set the setting
receiving function blocks in the application configuration to enable GOOSE
communication.
Note that the engineered data is written to the IED when executing a common
Write to IED operation.
© Copyright 2011 ABB. All rights reserved
Operation to Enabled in PST for all included GOOSE
Figure
70.
1MRK 511 245-UUS A
650 series
Engineering manual