Diagnostics and troubleshooting
90
Diagnostic information
The fault can be identified using the diagnostic information. The short text helps you by
providing information about the fault.
Status signal
Example
12.4.2

Calling up remedy information

Remedy information is provided for every diagnostic event to ensure that problems can be
rectified quickly:
• On the home page
Remedy information is displayed in a separate field below the diagnostics information.
• In the Diagnostics menu
Remedy information can be called up in the working area of the user interface.
The user is in the Diagnostics menu.
1. Call up the desired parameter.
2. On the right in the working area, mouse over the parameter.
 A tool tip with remedy information for the diagnostic event appears.
12.5

Adapting the diagnostic information

12.5.1

Adapting the diagnostic behavior

Each item of diagnostic information is assigned a specific diagnostic behavior at the
factory. The user can change this assignment for certain diagnostic information in the
Diagnostic behavior submenu .
Diagnostic behavior in accordance with Specification PROFIBUS Profile 3.02,
Condensed Status.
Expert → System → Diagnostic handling → Diagnostic behavior
Available diagnostic behaviors
The following diagnostic behaviors can be assigned:
Diagnostic behavior
Alarm
Warning
Logbook entry only
Off
Diagnostic information
Diagnostic code
Diagnostic number
842
A0013958
3-digit number
Description
Measurement is interrupted. The totalizers assume the defined alarm
condition. A diagnostic message is generated.
Measurement is resumed. Measured value output via PROFIBUS and totalizers
are not affected. A diagnostics message is generated.
The device continues to measure. The diagnostic message is entered in the
Event logbook (events list) submenu only and is not displayed in alternation
with the measured value display.
The diagnostic event is ignored, and no diagnostic message is generated or
entered.