Proline Cubemass C 100 PROFIBUS DP
Endress+Hauser
AI module (Analog Input)
Transmit an input variable from the measuring device to the PROFIBUS master (Class 1).
The selected input variable, along with the status, is cyclically transmitted to the
PROFIBUS Master (Class 1) via the AI module. The input variable is depicted in the first
four bytes in the form of a floating point number as per the IEEE 754 standard. The fifth
byte contains standardized status information pertaining to the input variable.
Eight Analog Input blocks are available (slot 1 to 8).
Selection: input variable
The input variable can be specified using the CHANNEL parameter.
CHANNEL
Input variable
32961
Mass flow
33122
Volume flow
33093
Corrected volume flow
708
Flow velocity
32850
Density
33092
Reference density
33101
Temperature
1042
Electronic temperature
901
Target fluid mass flow
793
Carrier mass flow
794
Concentration
263
Carrier tube temperature
1)
Only available with the Concentration application package
2)
Only available with the Heartbeat Verification application package
Factory setting
Function block
Factory setting
AI 1
Mass flow
AI 2
Density
AI 3
Temperature
AI 4
Volume flow
AI 5
Corrected volume flow
AI 6
Reference density
AI 7
Mass flow
AI 8
Mass flow
Data structure
Input data of Analog Input
Byte 1
Byte 2
Measured value: floating point number (IEEE 754)
1)
1)
1)
2)
Byte 3
Byte 4
System integration
Byte 5
Status
55