Electrical connection
32
7.3.2

Ensuring potential equalization

Requirements
No special measures for potential equalization are required.
For devices intended for use in hazardous locations, please observe the guidelines in
the Ex documentation (XA).
7.4

Special connection instructions

7.4.1

Connection examples

PROFIBUS DP
1
2
A
B
 10
Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1
Control system (e.g. PLC)
2
Cable shield provided at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications
3
Distribution box
4
Transmitter
If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must
continue as far as the terminal wherever possible.
7.5

Hardware settings

7.5.1

Setting the device address

PROFIBUS DP
The address must always be configured for a PROFIBUS DP/PA device. The valid address
range is between 1 and 126. In a PROFIBUS DP/PA network, each address can only be
assigned once. If an address is not configured correctly, the device is not recognized by the
master. All measuring devices are delivered from the factory with the device address 126
and with the software addressing method.