System integration
56
TOTAL module
Transmit a totalizer value from the measuring device to the PROFIBUS master (Class 1).
A selected totalizer value, along with the status, is cyclically transmitted to a PROFIBUS
Master (Class 1) via the TOTAL module. The totalizer value is depicted in the first four
bytes in the form of a floating point number as per the IEEE 754 standard. The fifth byte
contains standardized status information pertaining to the totalizer value.
Three Totalizer blocks are available (slot 9 to 11).
Selection: totalizer value
The totalizer value can be specified using the CHANNEL parameter.
CHANNEL
Input variable
32961
Mass flow
33122
Volume flow
33093
Corrected volume flow
901
Target fluid mass flow
793
Carrier mass flow
1)
Only available with the "Concentration" application package
Factory setting
Function block
Totalizer 1, 2 and 3
Data structure
Input data of TOTAL
Byte 1
Byte 2
Measured value: floating point number (IEEE 754)
SETTOT_TOTAL module
The module combination consists of the SETTOT and TOTAL functions:
• SETTOT: Control the totalizers via the PROFIBUS master.
• TOTAL: Transmit totalizer value, along with the status, to the PROFIBUS master.
Three Totalizer blocks are available (slot 9 to 11).
Selection: control totalizer
Value SETTOT
0
1
2
Factory setting
Function block
Totalizer 1, 2 and 3
Proline Cubemass C 100 PROFIBUS DP
1)
1)
Factory setting: TOTAL
Mass flow
Byte 3
Byte 4
Control totalizer
Totalize
Resetting
Adopt totalizer initial setting
Factory setting: Value SETTOT (meaning)
0 (totalizing)
Byte 5
Status