Commissioning
Parameter
Assign process variable
Low value partial filled pipe
detection
High value partial filled pipe
detection
Response time part. filled pipe
detect.
70
10.4.7
Configuring the partial filled pipe detection
The Partially filled pipe detection submenu contains parameters that have to be set for
configuring empty pipe detection.
Navigation
"Setup" menu → Partially filled pipe detection
Partially filled pipe detection
Assign process variable
Low value partial filled pipe detection
High value partial filled pipe detection
Response time part. filled pipe detect.
Parameter overview with brief description
Prerequisite
A process variable is selected
in the Assign process variable
parameter (→  70).
A process variable is selected
in the Assign process variable
parameter (→  70).
A process variable is selected
in the Assign process variable
parameter (→  70).
Description
Select process variable for
partially filled pipe detection.
Enter lower limit value for
deactivating partialy filled pipe
detection.
Enter upper limit value for
deactivating partialy filled pipe
detection.
Enter time before diagnostic
message is displayed for
partially filled pipe detection.
Proline Cubemass C 100 PROFIBUS DP
Selection / User
Factory setting
entry
• Off
Off
• Density
• Reference density
Signed floating-point
200
number
Signed floating-point
6 000
number
0 to 100 s
1 s
Endress+Hauser
→  70
→  70
→  70
→  70