9.1 Asynchronous motor startup wizard (with the integrated keypad)

The ADL300 can operate with regulation modes: Voltage/Frequency (SSC) , Sensorless (open loop) and field-oriented
vector control (closed loop).
Note!
Before starting, check the factory settings:
Menu 02 DRIVE INFO, parameter 02.2 Control type, PAR: 480, default=11.
0 2
.88.
Enter
Menu 04 DRIVE CONFIG, parameter 04.2 Regulation mode, PAR: 552, default=SSC control.
0 4
.88.
Enter
The STARTUP WIZARD is a guided procedure used for quick start-up of the drive that helps to set the main
parameters.
It consists of a series of questions, relating to the various sequences for entering and calculating the parameters
necessary for correct drive and lift application operation. The order of these sequences is as follows:
Electrical connections
Setting motor parameters
Autotune with motor at stand-still or coupled to the load
Setting encoder parameters (with control mode=Flux vector CL)
Setting the maximum speed reference and maximum system speed
Setting system weights
Setting application parameters
Saving parameters
The format of the function selection page is as follows:
0
3.8 8.
Enter
Pressing the Enter key, the function to be programmed is accessed.
Press the ▼ (Down) key to move to the next function skipping the current function.
Press the ▲ (Up) key to return to the previous function.
To terminate the sequence of functions and return to the menu, press the Prg key.
The end of the start-up sequence is indicated with the page:
.
.
d o
n E
Press the Prg key to exit the sequence and return to the menu.
Step 1 - Electrical connections
Make the connections as described in paragraph 7.3.2.
Checks to be performed before powering the drive
Check that the supply voltage is correct and that the input terminals on the drive (L1, L2 and L3) are connected
correctly.
Check that the output terminals on the drive (U, V and W) are connected to the motor correctly.
Check that all the drive control circuit terminals are connected correctly. Check that all control inputs are open.
Powering the drive
After completing all the checks described above, power the drive and proceed to step 2.
84.80.
8 8.
1
1.
Enter
85.52.
8
8.80
Enter
.
8 .
Πo
t
ADL300 • Quick installation guide - Specifications and connection
.
See step 1
See step 2
See step 3
See step 4
See step 6
See step 7
See step 8
See step 9