gefran installationSIEIDrive ADL300 Quick Start Up Manual, Specification And Installation page 89

Vector inverter for lifts with ynchronous/asynchronous motors
Table of Contents

Advertisement

Step 1 - Electrical connections
Make the connections as described in paragraph 7.3.2.
Checks to be performed before powering the drive
Check that the supply voltage is correct and that the input terminals on the drive (L1, L2 and L3) are connected
correctly.
Check that the output terminals on the drive (U, V and W) are connected to the motor correctly.
Check that all the drive control circuit terminals are connected correctly. Check that all control inputs are open.
Powering the drive
After completing all the checks described above, power the drive and proceed to step 2.
Step 2 - Setting motor parameters
Note!
Def: The factory (default) setting depends on the size of the drive that is connected. These values refer to the ADL..-1055-AC
03 STARTUP WIZARD
Set motor data?
E=Yes
Down=Next
Set the plate data of the motor connected, according to the procedures described on the previous pages.
Rated voltage [V]:
Rated current [A]:
Rated speed [rpm]:
Rated frequency [Hz]:
Pole pairs:
Rated power [kW]:
Rated power factor:
SEQ
01
PAR: 2000
E
Rated voltage
400
Def:
400
SEQ
02
PAR: 2002
Rated current
11.8
Def:
11.8
SEQ
03
PAR: 2004
Rated speed
1450
Def:
1450
SEQ
04
PAR: 2006
Rated frequency
50
Hz
Def:
50
SEQ
05
PAR: 2008
Pole pairs
2
Def:
2
SEQ
06
PAR: 2010
Rated power
5.50
Def:
5.50
SEQ
07
PAR: 2012
Rated power factor
0.83
Def:
0.83
the rated voltage of the motor indicated on the data plate.
motor rated current; approximately, the value should not be less than 0.3 times the rated current of the drive, output current class 1 @ 400 V
on the data plate of the drive.
rated speed of the motor; this value must reflect the speed of the fully loaded motor at rated frequency. If slip is indicated on the motor data
plate, set the Rated speed parameter as follows: Rated speed = Synchronous speed - Slip (e.g. for a 4-pole motor Rated speed = 1500 - 70
= 1430).
rated frequency of the motor, as shown on the data plate (asynchronous motors only).
Number of motor pole pairs. The number of motor pole pairs is calculated using the plate data and the following formula:
P = 60 [s] x f [Hz] / nN [rpm]
Where:
P = motor pole pairs, f = motor rated frequency (e.g. 50); nN = motor rated speed (e.g. 1450)
Motor rated power; for a motor data plate with an HP power value, set the rated power kW = 0.736 x the motor power HP value.
Leave the default rated power factor if the data are not available on the data plate.
ADL300 • Quick installation guide - Specifications and connection
SEQ
01
PAR:
E
Rated voltage
000000400
V
Def:
400
SEQ
02
PAR:
E
Rated current
00000011.8
A
Def:
11.8
SEQ
03
PAR:
E
Rated speed
0000001450
r p m
Def:
1450
SEQ
04
PAR:
E
Rated frequency
000000050
Def:
50
SEQ
05
PAR:
E
Pole pairs
Def:
2
SEQ
06
PAR:
E
Rated power
0000005.50
kW
Def:
5.50
SEQ
07
PAR: 2012
E
Rated power factor
0.83
Def:
0.83
401 V
2000
v
399 V
11.9 A
2002
A
11.7 A
1451 rpm
2004
1449 rpm
r p m
51 Hz
2006
49 Hz
Hz
3
2008
2
1
5.51 kW
2010
kW
5.49 kW
0.84
0.82
E
E
E
E
E
E
E
89

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sieidrive adl300Sieidrive adl300 advancedSieidrive adl300 basicSieidrive adl300aSieidrive adl300b