10.3 Messages
Note !
For more information see chapter 8.7.
Index
Error message shown on
the display [on the inte-
grated keypad]
Load default param [LDEF]
1
Option detect slot 1 [OPT1]
2
Option detect slot 2 [OPT2]
3
4
Option detect slot 3 [OPT3]
5
Autotune (motor)
[SLFT]
5
Autotune
(phasing)
(Only Synchronous)
[SLFT]
114
Sub-code
Condition: may occur during loading of the parameter database saved in flash
normally appears in the following conditions: at initial power-on when a new firmware version is downloaded, when the regulation is installed on a new
size, when the region is changed.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the parameter database saved in Flash.
If this message is displayed, the drive automatically performs the Load default command.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The database saved refers to a different size from the current size
0004H-4
The database saved refers to a different region from the current region
Solution: Set the parameters to the value required and perform Save parameter
Condition: when the drive is turned on it recognises the presence of an optional card. One of the messages is shown on the display for a few seconds
0H-0
None
0004H-4
Can
0008H-8
Enc 1 EXP-DE-I1R1F2-ADL
0108H-264
Enc 2 EXP-SE-I1R1F2-ADL
0208H-520
Enc 3 EXP-SESC- I1R1F2-ADL
0308H-776
Enc 4 EXP-EN/SSI- I1R1F2-ADL
0408H-1032
Enc 5 EXP-HIP- I1R1F2-ADL
0101H-257
I/O 1 EXP-IO-D4-ADL
0501H-1281
I/O 1 EXP-IO-D8R4-ADL
0901H-2305
I/O 1 EXP-IO-D16R4-ADL
0F01-3841
I/O 1 EXP-IO-D12A2R4-ADL
1301H-4865
I/O 1 EXP-IO-D8A4R4-ADL
1501H-5377
I/O 1 EXP-IO-D6R2-F-ADL
00FFH-255
Unknown
Solution:
Condition: this may occur during the self-tuning procedure
0
No error
1
N.A.
2
N.A.
The motor plate data parameters have changed but the Take parameters command, PAR 2020, has not been executed
3
Solution: Execute the Take parameters command.
The motor is not connected
4
Solution: Connect the motor
While running self-tuning the ESC key was pressed or the enable contact was opened or an alarm occurred. The self-tuning command
was sent with the drive in the alarm condition
5
Solution: Eliminate the reason for the alarm, remove the reason for the opening of the enable contact, reset alarms.
A setting performed by the self-tuning function produced a parameter value outside the min or max range.
6
Solution: Check the motor plate data or drive and motor sizes have been combined incorrectly.
The self-tuning command was sent without being enabled.
7
Solution: Close the enable contact before sending the self-tuning command
A setting performed by self-tuning has reached a measurement method limit
8 ... 21
Solution: Check the motor plate data or the drive and motor sizes have been combined incorrectly.
The Enable was not given or removed in time during the phasing procedure.
30
Solution: Repeat the phasing procedure and check the connection of the enable signals.
Solution: If the message appears with a value other than 0, follow the instructions supplied for each particular case and repeat self-tuning. This should
be performed using the wizard function available from the keypad (STARTUP WIZARD) and the Tool software on the PC.
Pay attention to all motor plate data parmaeters, especially:
- Rated speed, Motor rated speed in rpm.
•
(ADL300 for Asynchronous motor) Take care not to set the Rated speed parameter to the synchronous speed. The value of the Rated speed
parameter must be less than: [(Rated frequency * 60) / Pole pairs].
•
(ADL300 for Synchronous motor) Take care to set the Rated speed parameter to the synchronous speed.
- Rated frequency, Motor rated frequency in Hz
- Pole pairs, Motor pole pairs
If the problem persists even after following the instructions supplied, confirm the values of the motor plate data parameters, execute the Take param-
eters command but not self-tuning.
0
No error
The encoder card in use cannot manage automatic phasing.
40
Solution: Use the appropriate encoder card
Incorrect Incremental encoder impulse count
41
Solution: Check the electric signals of the incremental encoder. Check the value of the encoder impulse parameter
Incorrect absolute encoder impulse count
42
Solution: Check the electric signals of the absolute encoder. Check the configuration of the absolute encoder
ADL300 • Quick installation guide - Specifications and connection
Description