10.3 Messages

Note !
For more information see chapter 8.7.
Index
Error message shown on
the display [on the inte-
grated keypad]
Load default param [LDEF]
1
Option detect slot 1 [OPT1]
2
Option detect slot 2 [OPT2]
3
4
Option detect slot 3 [OPT3]
5
Autotune (motor)
[SLFT]
5
Autotune
(phasing)
(Only Synchronous)
[SLFT]
114
Sub-code
Condition: may occur during loading of the parameter database saved in flash
normally appears in the following conditions: at initial power-on when a new firmware version is downloaded, when the regulation is installed on a new
size, when the region is changed.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the parameter database saved in Flash.
If this message is displayed, the drive automatically performs the Load default command.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The database saved refers to a different size from the current size
0004H-4
The database saved refers to a different region from the current region
Solution: Set the parameters to the value required and perform Save parameter
Condition: when the drive is turned on it recognises the presence of an optional card. One of the messages is shown on the display for a few seconds
0H-0
None
0004H-4
Can
0008H-8
Enc 1 EXP-DE-I1R1F2-ADL
0108H-264
Enc 2 EXP-SE-I1R1F2-ADL
0208H-520
Enc 3 EXP-SESC- I1R1F2-ADL
0308H-776
Enc 4 EXP-EN/SSI- I1R1F2-ADL
0408H-1032
Enc 5 EXP-HIP- I1R1F2-ADL
0101H-257
I/O 1 EXP-IO-D4-ADL
0501H-1281
I/O 1 EXP-IO-D8R4-ADL
0901H-2305
I/O 1 EXP-IO-D16R4-ADL
0F01-3841
I/O 1 EXP-IO-D12A2R4-ADL
1301H-4865
I/O 1 EXP-IO-D8A4R4-ADL
1501H-5377
I/O 1 EXP-IO-D6R2-F-ADL
00FFH-255
Unknown
Solution:
Condition: this may occur during the self-tuning procedure
0
No error
1
N.A.
2
N.A.
The motor plate data parameters have changed but the Take parameters command, PAR 2020, has not been executed
3
Solution: Execute the Take parameters command.
The motor is not connected
4
Solution: Connect the motor
While running self-tuning the ESC key was pressed or the enable contact was opened or an alarm occurred. The self-tuning command
was sent with the drive in the alarm condition
5
Solution: Eliminate the reason for the alarm, remove the reason for the opening of the enable contact, reset alarms.
A setting performed by the self-tuning function produced a parameter value outside the min or max range.
6
Solution: Check the motor plate data or drive and motor sizes have been combined incorrectly.
The self-tuning command was sent without being enabled.
7
Solution: Close the enable contact before sending the self-tuning command
A setting performed by self-tuning has reached a measurement method limit
8 ... 21
Solution: Check the motor plate data or the drive and motor sizes have been combined incorrectly.
The Enable was not given or removed in time during the phasing procedure.
30
Solution: Repeat the phasing procedure and check the connection of the enable signals.
Solution: If the message appears with a value other than 0, follow the instructions supplied for each particular case and repeat self-tuning. This should
be performed using the wizard function available from the keypad (STARTUP WIZARD) and the Tool software on the PC.
Pay attention to all motor plate data parmaeters, especially:
- Rated speed, Motor rated speed in rpm.
(ADL300 for Asynchronous motor) Take care not to set the Rated speed parameter to the synchronous speed. The value of the Rated speed
parameter must be less than: [(Rated frequency * 60) / Pole pairs].
(ADL300 for Synchronous motor) Take care to set the Rated speed parameter to the synchronous speed.
- Rated frequency, Motor rated frequency in Hz
- Pole pairs, Motor pole pairs
If the problem persists even after following the instructions supplied, confirm the values of the motor plate data parameters, execute the Take param-
eters command but not self-tuning.
0
No error
The encoder card in use cannot manage automatic phasing.
40
Solution: Use the appropriate encoder card
Incorrect Incremental encoder impulse count
41
Solution: Check the electric signals of the incremental encoder. Check the value of the encoder impulse parameter
Incorrect absolute encoder impulse count
42
Solution: Check the electric signals of the absolute encoder. Check the configuration of the absolute encoder
ADL300 • Quick installation guide - Specifications and connection