5.4 External braking resistors (optional)

Recommended combinations for use with internal braking unit.
Size
1040
1055
2075
2110
3150
3185
3220
4300
4370
4450
5550
5750
2055
3075
3110
4150
4185
4220
5300
5370
1011
1015
2022
2030
3040
3055
P
nbr
R
br
E
br
Braking resistors may be subject to unexpected overloads due to faults.
Resistors MUST be protected using thermal cutouts. These devices must not interrupt the circuit in which the resistor is
inserted but their auxiliary contact must cut off the power supply to the power section of the drive. If the resistor requires a
Warning!
protection contact, this must be used together with that of the thermal cutout.
A la suite de pannes, les résistances de freinage peuvent être sujettes à des surcharges imprévues. La protection des résist-
ances au moyen de dispositifs de protection thermique est absolument capitale. Ces dispositifs ne doivent pas interrompre le
circuit qui abrite la résistance, mais leur contact auxiliaire doit couper l'alimentation du côté puissance du drive. Si la résist-
ance prévoit un contact de protection, ce dernier doit être utilisé conjointement à celui du dispositif de protection thermique.
28
Table 5.4.1: Recommended combination ADL...-AC and ADL...-BR series
Resistor type
Code
RFPD 750 DT 100R
S8SY4
RFPR 750 D 68R
S8SZ3
RFPR 750 D 68R
S8SZ3
RFPR 1200 D 49R
S8SZ4
RFPR 1900 D 28R
S8SZ5
BRT4K0-15R4
S8T00G
BRT4K0-15R4
S8T00G
BRT4K0-11R6
S8T00H
BRT4K0-11R6
S8T00H
BRT8K0-7R7
S8T00I
BRT8K0-7R7
S8T00I
RFPR 1200 D 49R
S8SZ4
RFPR 1900 D 28R
S8SZ5
BRT4K0-15R4
S8T00G
BRT4K0-11R6
S8T00H
BRT4K0-11R6
S8T00H
BRT8K0-7R7
S8T00I
BRT8K0-7R7
S8T00I
RF 220 T 100R
S8T0CE
RF 220 T 68R
S8T00T
RF 300 D 34R
S8T0CH
RF 300 D 34R
S8T0CH
RFPD 750 DT 26R
S8T0CZ
RFPD 750 DT 26R
S8T0CZ
Braking resistor rated power
Braking resistor ohmic value
Maximum energy that can be dissipated on the resistor
ADL300 • Quick installation guide - Specifications and connection
List and technical data of standard external resistors
Max. overload, 1"
Max. overload, 30"
Q.ty
- service 10%
- service 25%
E
(kJ)
E
(kJ)
br
br
ADL300-...-4, 3ph
1
7.5
38
1
7.5
38
1
7.5
28
1
7.5
28
1
12
43
1
40
150
1
40
150
1
40
150
1
40
150
1
40
150
1
40
150
External braking unit (BUy series, optional)
ADL300-...-2T, 3ph
1
12
43
1
19
75
1
40
150
1
40
150
1
40
150
1
40
150
1
40
150
External braking unit (BUy series, optional)
ADL300-...-2M, 1ph
1
1.5
11
1
1.5
11
1
2.5
24
1
2.5
24
1
4.5
43
1
4.5
43
P
R
Dimensions:
nbr
br
Housing
Width x Height x
Depth (mm)
(W)
(Ω)
750
100
IP44
200 x 70 x 106
750
68
IP44
245 x 75 x 100
750
68
IP44
245 x 75 x 100
1200
49
IP44
310 x 75 x 100
1500
28
IP44
365 x 75 x 100
4000
15.4
IP20
625 x 100 x 250
4000
15.4
IP20
625 x 100 x 250
4000
11.6
IP20
625 x 100 x 250
4000
11.6
IP20
625 x 100 x 250
8000
7.7
IP20
625 x 165 x 250
8000
7,7
IP20
625 x 165 x 250
1200
49
IP44
310 x 75 x 100
1500
28
IP44
365 x 75 x 100
4000
15.4
IP20
625 x 100 x 250
4000
11.6
IP20
625 x 100 x 250
4000
11.6
IP20
625 x 100 x 250
8000
7.7
IP20
625 x 165 x 250
8000
7.7
IP20
625 x 165 x 250
200
100
IP44
300 x 27 x 36
200
68
IP44
300 x 27 x 36
300
34
IP44
260 x 38 x 106
300
34
IP44
260 x 38 x 106
750
26
IP44
200 x 70 x 106
750
26
IP44
200 x 70 x 106
Weight
(kg)
1.7
2.7
2.7
4.2
4.2
7.0
7.0
7.0
7.0
10.0
10.0
4.2
4.2
7.0
7.0
7.0
10.0
10.0
0.5
-
1.4
1.4
1.7
1.7

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sieidrive adl300Sieidrive adl300 advancedSieidrive adl300 basicSieidrive adl300aSieidrive adl300b

Table of Contents