7.4

SENSOR SELECTION (TABLE 4)

No.
Items
Temperature
1
Sensor
Oil Pressure
2
Sensor
Fuel Level
3
Sensor
HGM1790N Genset Controller
HGM1790N GENSET CONTROLLER USER MANUAL
Content
0 Not used
1 Low digital input is active
2 High digital input is active
3 User defined resistor type
4 VDO
5 SGH (yellow river sensor)
6 SGD (Dongkang sensor )
7 CURTIS
8 DATCON
9 VOLVO-EC
10 SGX 120 DEGREE
0 Not used
1 Low digital input is active
2 High digital input is active
3 User defined resistor type
4 VDO 10Bar
5 SGH (yellow river sensor)
6 SGD(Dongkang sensor )
7 CURTIS
8 DATCON 10Bar
9 VOLVO-EC
10 SGX 10Bar
0 Not used
1 Low digital input is active
2 High digital input is active
3 User defined resistor type
4 SGH (yellow river sensor)
5 SGD (Dongkang sensor )
6 Reserved 1
7 Reserved 2
2017-10-09
Remark
Digital input is switch value signal; low
or high electrical level can be selected
to be active, connecting to earth point
will mean that low electrical level is
selected, hang in air means high
electrical level is selected; cannot be
connected to power supply positive.
The range of user-defined resistor type
sensor is 0-6000 Ohm, by default SGD
sensor is selected.
Digital input is switch value signal; low
or high electrical level can be selected
to be active, connecting to earth point
will mean that low electrical level is
selected, hang in air means high
electrical level is selected; cannot be
connected to power supply positive.
The range of user-defined resistor type
sensor is 0-6000 Ohm, by default SGD
sensor is selected.
Digital closed and Digital open both are
digital signal; low or high electrical level
can
be
selected
connecting to earth point will mean that
low electrical level is selected, hang in
air means high electrical level is
selected; cannot be connected to power
supply positive.
The range of user-defined resistor type
sensor is 0-6000 Ohm, by default "Not
used" is selected
Before selecting fuel level sensor type,
digital input type must be set as 8.
Version1.1
to
be
active,